Wire Gauge Calculator

Convert between AWG, mm² and diameter; look up ampacity from NEC Table 310.16 or IEC 60364-5-52 with ambient-temperature and bundling corrections; and size conductors for voltage drop over any run in feet or metres. Works for 12 V DC, 120/240 V single-phase and three-phase circuits.

① Size conversion — AWG ↔ mm² ↔ diameter

Area

3.309 mm²

6.53 kcmil

Diameter (solid equiv.)

2.053 mm

0.08081 in · 80.81 mil

AWG

12

Nearest standard: 12 AWG

Resistance (at conductor temp)

5.198 Ω/km

1.584 Ω/1000 ft

Next IEC 60228 metric size at or above this area: 4 mm². Stranded conductors are 5–15 % larger in outside diameter than solid wire of the same area; the diameter above is the solid-equivalent conductor.

② Ampacity (typical table values)

Table value

25 A

Correction factor

× 1

ambient × grouping

Corrected ampacity

25 A

NEC 240.4(D) small-conductor rule: regardless of the table, overcurrent protection may not exceed 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.

If terminals are only rated 60/75 °C (most breakers and lugs), you must use that column even with 90 °C wire. These are typical design values — actual installations must follow the NEC/CEC/BS 7671 or your local code and a qualified electrician.

③ Voltage drop & recommended size

Voltage drop

2.38 V

1.98 %

Voltage at load

117.6 V

Cable loss (heat)

35.6 W

0.356 W per ft of conductor

Verdict

Within target

target 3 %

Recommended size

  • Voltage drop alone needs at least 2.18 mm² → 2.5 mm² / 12 AWG
  • Ampacity (selected table) needs at least 14 AWG (2.08 mm²)

→ Meets both: 12 AWG (3.31 mm²)

The current is below the smallest table size; size by voltage drop, but check mechanical strength and the connector crimp range.

Reference table — AWG sizes, resistance and NEC ampacity
AWGDia. inDia. mmmm²kcmilΩ/1000 ft @20 °CNEC 60/75/90 °C (A)
300.010.2550.05090.101103—
280.01260.3210.0810.1664.7—
260.01590.4050.1290.25440.7—
240.02010.5110.2050.40425.6—
220.02530.6440.3260.64216.1—
200.0320.8120.5181.0210.1—
180.04031.020.8231.626.37— / — / 14
160.05081.291.312.584.01— / — / 18
140.06411.632.084.112.5215 / 20 / 25
120.08082.053.316.531.5820 / 25 / 30
100.1022.595.2610.40.99630 / 35 / 40
80.1283.268.3716.50.62740 / 50 / 55
60.1624.1213.326.30.39455 / 65 / 75
40.2045.1921.241.70.24870 / 85 / 95
30.2295.8326.752.60.19785 / 100 / 115
20.2586.5433.666.40.15695 / 115 / 130
10.2897.3542.483.70.124110 / 130 / 145
1/00.3258.2553.51060.098125 / 150 / 170
2/00.3659.2767.41330.0777145 / 175 / 195
3/00.4110.4851680.0617165 / 200 / 225
4/00.4611.71072120.0489195 / 230 / 260

Resistance is calculated for solid copper with ρ = 1.72×10⁻⁸ Ω·m; published stranded maxima (NEC Chapter 9 Table 8, IEC 60228) run slightly higher. NEC values: Table 310.16, ≤ 3 current-carrying conductors, 30 °C (86 °F) ambient.

How to use

  1. In ① pick AWG, mm² or diameter and enter a size — area, kcmil, diameter in inches/mm and resistance per 1,000 ft appear instantly.
  2. In ② choose the NEC 310.16 column (60/75/90 °C) or an IEC installation method, then set ambient temperature and the number of current-carrying conductors.
  3. In ③ enter circuit type, voltage, current, one-way length (ft or m) and your target drop.
  4. 'Recommended size' is the smallest standard gauge that satisfies both voltage drop and the selected ampacity table. Expand the reference table for the full AWG chart.

Basics

How AWG works — and how it maps to mm²

American Wire Gauge is a logarithmic numbering system: the bigger the number, the thinner the wire. It is anchored at 36 AWG = 0.005 in (0.127 mm) and 4/0 (0000) AWG = 0.4600 in, with 39 geometric steps in between. That gives three handy rules of thumb: every 3 gauges doubles (or halves) the cross-section, every 6 gauges doubles the diameter, and every 10 gauges changes resistance by roughly 10×. 10 AWG copper is about 1 Ω per 1,000 ft — memorise that one and you can estimate the rest. Outside North America, wire is specified by metric cross-section in mm² from the IEC 60228 series (0.5, 0.75, 1, 1.5, 2.5, 4, 6, 10, 16 mm² …), so when you source parts or read European and Asian datasheets you constantly convert between the two.

AWG diameter:   d = 0.127 mm × 92^((36 − n) / 39)     (1/0 = 0, 2/0 = −1, 3/0 = −2, 4/0 = −3)
Area:           A = π/4 × d²          circular mils = (d in mils)²
Resistance:     R' = ρ(T) / A,   ρ(T) = 1.72×10⁻⁸ × (1 + 0.00393 × (T − 20 °C))  Ω·m
Voltage drop:   Vd = k × I × R' × L       k = 2 (DC / single-phase), √3 (three-phase)
Minimum area:   A_min = k × I × L × ρ / (V × drop%)
n = gauge number, d = conductor diameter, ρ = copper resistivity (1.72×10⁻⁸ Ω·m at 20 °C / 68 °F, temperature coefficient 0.00393/°C), I = current, L = one-way length, V = source voltage. Reactance is ignored, so drops on very large AC feeders (above ~1/0) are slightly understated.

AWG quick reference

AWGDiameter (in / mm)Area mm² / kcmilΩ per 1,000 ft @ 20 °CNEC 310.16 75 °CTypical use
240.0201 / 0.5110.205 / 0.40425.6—Signal, Cat5e/6 conductors
220.0253 / 0.6440.326 / 0.64216.1—Hookup wire, sensors
180.0403 / 1.020.823 / 1.626.3714 A (90 °C col.)Lamp cord, LED strips
160.0508 / 1.291.31 / 2.584.0118 A (90 °C col.)Extension cords, auto accessories
140.0641 / 1.632.08 / 4.112.5220 A (15 A OCPD)15 A branch circuits
120.0808 / 2.053.31 / 6.531.5825 A (20 A OCPD)20 A circuits, inverters
100.1019 / 2.595.26 / 10.40.99635 A (30 A OCPD)30 A, dryers, solar strings
80.1285 / 3.268.37 / 16.50.62750 ARanges, high-current DC
40.2043 / 5.1921.2 / 41.70.24885 ABattery cables, sub-panels
Resistance is calculated for solid copper with ρ = 1.72×10⁻⁸ Ω·m; NEC Chapter 9 Table 8 lists stranded values a little higher (e.g. 1.24 Ω/kft for 10 AWG at 75 °C, which also includes the temperature rise). OCPD = maximum overcurrent protection under NEC 240.4(D).

Ampacity

Ampacity is really an insulation temperature limit

Copper won't melt at any current you'd sensibly run, but its insulation will: PVC/THHN-class insulation is rated 60, 75 or 90 °C. Ampacity is the current at which I²R heating balances heat loss so the conductor stays at that rating. That's why NEC Table 310.16 has three columns, and why it assumes no more than three current-carrying conductors in a raceway or cable at 30 °C (86 °F) ambient. More conductors bundled together get the 310.15(C)(1) adjustment (4–6 → 80 %, 7–9 → 70 %, 10–20 → 50 %), and hotter ambients get the 310.15(B) correction, √((Tc − Ta)/(Tc − 30)) — 0.88 for a 75 °C conductor at 40 °C. Two traps catch people every day: 110.14(C) says that if terminals are only rated 60/75 °C (most breakers and lugs), you must use that column even with 90 °C wire; and 240.4(D) caps the breaker at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper regardless of the table. For metric wire the calculator also offers IEC 60364-5-52 Table B.52.4 (PVC, 70 °C conductor), the basis for BS 7671 and most national codes outside the US.

Worked examples

When voltage drop, not ampacity, picks the wire

  • 12 V DC, 20 A load, 10 ft from the battery, 3 % target (0.36 V): A_min = 2 × 20 × 3.048 m × 1.72×10⁻⁸ ÷ 0.36 = 5.83 mm². 10 AWG (5.26 mm²) falls short, so use 8 AWG (8.37 mm²). Ampacity alone would have allowed 12 AWG, which drops 0.63 V (5.3 %); 14 AWG would drop 1.0 V (8.4 %).
  • 120 V single-phase, 15 A, 100 ft one-way, 3 % (3.6 V): A_min = 2 × 15 × 30.48 × 1.72×10⁻⁸ ÷ 3.6 = 4.37 mm², i.e. 10 AWG instead of the 14 AWG the 15 A breaker would otherwise allow. Long garage and shed runs are where this bites.
  • Same power at 240 V instead of 120 V: half the current and twice the allowable drop, so a quarter of the copper area. That's why EV chargers, well pumps and long feeders run at 240 V.

Pitfalls

Common mistakes

  • Entering the round-trip length: the calculator wants the one-way distance and applies the return conductor itself (k = 2). Entering 2 × the run doubles the result.
  • Trusting 'chassis wiring' charts: the widely copied table claiming 10 AWG = 55 A assumes a single wire in free air at high conductor temperature, with no published basis. Inside a bundle, conduit or a hot enclosure it is dangerous.
  • Ignoring termination ratings: 90 °C wire on a 75 °C breaker is a 75 °C circuit. Use the 90 °C column only as the starting point for derating.
  • Rounding mm² down when substituting: replacing 12 AWG (3.31 mm²) with 2.5 mm² wire adds 32 % resistance. Always go to the same or larger area — 4 mm².
  • Forgetting crimp ranges: terminals are rated for a specific gauge span (for example 28–22 AWG) printed in the contact datasheet. Oversized wire crimps badly and the terminal overheats first.
  • Treating aluminium like copper: aluminium's resistivity is about 2.82×10⁻⁸ Ω·m (1.64× copper), roughly two AWG sizes larger for the same drop. This calculator is copper-only.

In practice

Tips from KEMI's bench

On electronics harnesses the current rating is set by the weakest of three links: the wire, the connector contact and the PCB trace. A 0.1 in (2.54 mm) header pin is good for about 3 A, a JST XH contact 3 A and a PH contact 2 A, so upsizing the wire often just moves the bottleneck to the connector. Parallel several pins or switch to a terminal block for high-current paths, and size the copper on the board with our PCB trace width calculator. When you order a harness, specify it fully — 'UL1007 22 AWG red, 150 mm, XH crimp both ends' — to avoid a second round. For 12–24 V systems carrying tens of amps (vehicles, solar, robotics), voltage drop almost always governs, so check the voltage-drop minimum before you look at any ampacity table.

FAQ

What size wire do I need for 20 amps?

For a typical 20 A branch circuit, 12 AWG copper — NEC 240.4(D) limits 12 AWG to a 20 A breaker, and its 75 °C ampacity is 25 A. On long runs (roughly over 70–80 ft at 120 V) voltage drop pushes you to 10 AWG; plug your length into the calculator.

What is 10 AWG in mm²?

10 AWG is 2.588 mm in diameter and 5.26 mm² in area (10,380 circular mils). The nearest IEC metric size that's at least as large is 6 mm²; 4 mm² would be undersized.

Why do 'chassis wiring' charts show much higher amps?

They assume a single conductor in free air with a high allowable temperature rise, and their origin is undocumented. They may be fine for a short jumper inside a ventilated chassis, but not for bundles, conduit or building wiring — use NEC 310.16 or IEC tables with correction factors.

How much voltage drop is acceptable?

The NEC's informational notes (210.19(A) and 215.2(A)) suggest no more than 3 % on a branch circuit and 5 % total including the feeder. They're recommendations, not requirements, but most designers follow them; for 12 V electronics aim for 3 % or less.

Do I enter one-way or round-trip length?

One-way — the distance from the source to the load. The calculator multiplies by 2 for DC and single-phase (out and back) and by √3 for three-phase line-to-line.

Can I use this for aluminum wire?

No, it's copper-only. Aluminum has about 1.64× the resistivity of copper, so you need roughly two AWG sizes larger for the same voltage drop, plus AL-rated terminals and anti-oxidant compound.